It’s a structural test of the extinguisher’s cylinder, checking whether the shell can safely hold pressure well above its normal operating level.
The cylinder is emptied, pressurized to one and a half times its rated working pressure, and monitored for expansion or leaks. This is separate from the annual inspection or 6-year maintenance, testing the physical integrity of the shell itself rather than the extinguisher’s internal components or charge.
The interval depends on the cylinder type, generally every 5 years for water, foam, and CO2 units, and every 12 years for stored-pressure dry chemical units.
Exact intervals vary by manufacturer and construction, which is why the specific requirement gets confirmed against the stamped manufacture date during service rather than assumed from a general rule of thumb.
A cylinder that fails hydrostatic testing is condemned and removed from service immediately, with no partial pass or repair option.
This isn’t a deficiency that gets patched. If the shell can’t safely hold pressure, the unit is replaced rather than returned to service under any circumstances.